Error code 273
Foldingpoti wire break
Alarm at Drill and Maestro.Drill (273-1)
since version 10.13
Maestro (273-2)
since version 10.13
When does the alarm occur?
While automatic folding (folding in/unfolding) is active, the wing potentiometer signals a value smaller than 2 mA.
Does a Drilling error (drilling drop-out) occur?
No.
What to do?
- Check the wiring.
- Check the wing potentiometer.
- If the wiring of the wing potentiometer is defective, fold in or unfold manually via diagnostic. Follow the notes in the operating instructions.
Is there an audible indication?
3 successive acoustic signals
How is the alarm confirmed?
Press ESC to confirm